SPECIFICATION FOR ELECTRICAL CABLES
SPECIFICATION FOR ELECTRICAL CABLES
This specification covers the minimum requirements for the design, manufacture and testing of high and
low voltage power cables, control and earthing cables for the SOUTH PARS GAS FIELD
DEVELOPMENT PHASES 20 & 21, ASSALUYEH / SOUTH PARS GAS FIELD PERSIAN GULF,
IRAN.
Electrical system voltages
33kV 50 Hz 3 phases neutral resistance earthed
11kV 50 Hz 3 phases neutral resistance earthed
6kV 50 Hz 3 phases neutral resistance earthed
400V 50 Hz 3 phases solidly earthed
230V 50 Hz 1 phases solidly earthed (lighting system)
230V 50 Hz 1 phases isolated from earth (UPS system)
48VDC - unearthed
Environmental conditions
Environmental conditions shall be as per Basic Engineering Design Data, "DB-SP2021-ON-PR-999-P332-
0204".
Nevertheless all equipment shall be capable of continuous operation at 48°C without deleterious effect.
Insulating material Insulation grade– service voltages
33kV system 19/33 kV (36 kV) (XLPE)2 or (EPR)1 for LV cables.
11kV system 8.7/15 kV (17.5 kV)
6kV system 6/10 kV (12 kV)
400V/230V systems 600/1000V
48VDC 600/1000V
Polyvinyl chloride (PVC) optional for internal air conditioned building use only.
Insulation withstanding XLPE PVC
70ºC 90ºC at 100% continuous load
160°C 250°C during short circuit
5.3 Cross sections
• Minimum cable cross section shall be:
- 1.5 sqmm for RTD cables
- 2.5 sqmm for control (digital signal)
- 2.5 sqmm for LV power and lighting cables
- 1 sqmm for analogue signals
- 35 sqmm for MV power cables
• For high voltage, the following cross sections shall not be exceeded:
- 240 sqmm for three-core armoured cables
- 300 sqmm for single core cables
• For low voltage the limits shall be:
- 240 sqmm for a cable whether armoured or not, up to a maximum of three conductors
- 400 sqmm for single core cables
• Multi-conductor cables
Cross section of phase cores (sqmm) Cross section of neutral cores (sqmm)
S S<=25
16 35
25 50
35 70
50 95
70 120
70 150
95 185
120 240
300 150
- When a multi-conductor cable includes a protective core, it shall be sized according to the following
table:
Cross section of phase cores (sqmm) Cross section of protective cores
S ≤ 16 S
16 < S ≤ 35 16
S/2 S ≥ 50